Tank Compliance Inspection (Lawrence Co-op Bid)
General Information
Information
Date
Is Tank Registered?
Select Option
Y
N
Facility I.D. #
Facility Name
Facility Address
Facility Phone Number
Facility Owner Name
Facility Owner Address
Type of Owner
Type of Petroleum Facility
Select Option
01 - Storage Terminal/Petrol. Distributor
02 - Retail Gasoline Sales
03 - Other Retail Sales
04 - Manufacturing
05 - Utility
06 - Trucking/Transportation/Fleet
07 - Apartment/Office Building
08 - School
09 - Farm
10 - Private Residence
11 - Airline/Air Taxi/Airport
12 - Chemical Distributor
13 - Municipality
15 - Railroad
25 - Auto Service/Repair (No Gasoline
26 - Religious (Church, Synagogue, Mosque, Temple, etc.)
27 - Hospital/Nursing Home/Health Care
28 - Cemetery/Memorial
52 - Marina
53 - Nuclear Power Plant
99 - Other
Tax Map Info
Federal Tax ID No
Inspector
Facility Rep Name
Facility Rep Title
Facility Rep Phone
Facility Rep Company Name
Facility Rep Address
Class A Operator Name
Class A Operator Auth #
Class A Operator Title
Class B Operator Name
Class B Operator Auth #
Class B Operator Title
Asset Information
Information
Tank System Category
Select Option
CAT1 (Installed before Dec 27, 1986)
CAT2 (Installed between Dec 27, 1986 to Oct 11, 2015)
CAT3 (Installed after Oct 11, 2015)
Tank Type
Select Option
UST
AST
Is the inspection announced or unannounced?
Select Option
Announced
Unannounced
Is the registration certificate posted a the facility?
Select Option
Y
N
No Access
Is the registration information current and correct?
Select Option
Y
N
Expired Registration
Unregistered Facility
Unregistered Tank
Tank Diameter/Dimensions
Tank Size
Tank Contents
Tank Installed Date
Tank Manufacturer
Material of Construction
Tank Service or Use
Tank Monitoring System (TMS) Make
TMS Model
TMS Serial #
Is there a Printer?
Select Option
Y
N
Other Equipment (RA, Gauge, Sensors, Probes, Alarms etc.)
Other Equipment 1 Name
Other Equipment 1 Make
Other Equipment 1 Model
Other Equipment 1 Serial #
Other Equipment 2 Name
Other Equipment 2 Make
Other Equipment 2 Model
Other Equipment 2 Serial #
Other Equipment 3 Name
Other Equipment 3 Make
Other Equipment 3 Model
Other Equipment 3 Serial #
Other Equipment 4 Name
Other Equipment 4 Make
Other Equipment 4 Model
Other Equipment 4 Serial #
Manhole #1 Make
Manhole #1 Model
Manhole #1 Diameter
Manhole #2 Make
Manhole #2 Model
Manhole #2 Diameter
Manhole #3 Make
Manhole #3 Model
Manhole #3 Diameter
Manhole #4 Make
Manhole #4 Model
Manhole #4 Diameter
Fuel Management System Make
Fuel Management System Model
Fuel Management System Serial #
Tank Registration Information
Information
1. Action
Select Option
1. Initial Listing
2. Add Tank
3. Close/Remove Tank
4. Information Correction
5. Repair/Reline Tank
6. Inspection
2. Tank #
3. Tank Location
Select Option
1. Aboveground - contact with soil
2. Aboveground - contact with impervious barrier
3. Aboveground on saddles, legs, stilts, rack or cradle
4. Partially buried tank (tank with 10% or more below ground)
5. Underground including vaulted with no access for inspection
6. Aboveground in Subterranean Vault with access for inspections
4. Tank Status
Select Option
1. In-service
2. Out-of-service
3. Closed-Removed
4. Closed- In Place
5. Tank converted to Non-Regulated use
5. Date Installed
6. Tank Capacity (Gallons)
7. Product Stored
Select Option
Heating Oils: On-Site Consumption 0001. #2 Fuel Oil
Heating Oils: On-Site Consumption 0002. #4 Fuel Oil
Heating Oils: On-Site Consumption 0259. #5 Fuel Oil
Heating Oils: On-Site Consumption 0003. #6 Fuel Oil
Heating Oils: On-Site Consumption 0012. Kerosene
Heating Oils: On-Site Consumption 0591. Clarified Oil
Heating Oils: On-Site Consumption 2711. Biodiesel (Heating)
Heating Oils: On-Site Consumption 2642. Used Oil (Heating)
Heating Oils: Resale/Redistribution 2718. #2 Fuel Oil
Heating Oils: Resale/Redistribution 2719. #4 Fuel Oil
Heating Oils: Resale/Redistribution 2720. #5 Fuel Oil
Heating Oils: Resale/Redistribution 2721. #6 Fuel Oil
Heating Oils: Resale/Redistribution 2722. Kerosene
Heating Oils: Resale/Redistribution 2723. Clarified Oil
Motor Fuels 0009. Gasoline
Motor Fuels 2712. Gasoline/Ethanol
Motor Fuels 008. Diesel
Motor Fuels 2710. Biodiesel
Motor Fuels 0011. Jet Fuel
Motor Fuels 1044. Jet Fuel (Biofuel)
Motor Fuels 2641. Aviation Gasoline
Lubricating/Cutting Oils 0013. Lube Oil
Lubricating/Cutting Oils 0015. Motor Oil
Lubricating/Cutting Oils 1045. Gear/Spindle Oil
Lubricating/Cutting Oils 0010. Hydraulic Oil
Lubricating/Cutting Oils 0007. Cutting Oil
Lubricating/Cutting Oils 0021. Transmission Fluid
Lubricating/Cutting Oils 1836. Turbine Oil
Lubricating/Cutting Oils 0308. Petroleum Grease
Oils Used as Building Materials 2626. Asphaltic Emulsions
Oils Used as Building Materials 0748. Form Oil
Petroleum Spirits 0014. White/Mineral Spirits
Petroleum Spirits 1731. Naphtha
Mineral/Insulating Oils 0020. Insulating Oil (e.g., Transformer, Cable Oil)
Mineral/Insulating Oils 2630. Mineral Oil
Waste/Used/Other Oils 0022. Waste/Used Oil
Waste/Used/Other Oils 9999. Other-Please list
Crude Oil 0006. Crude Oil
Crude Oil 0701. Crude Oil Fractions
Emergency Generator Fuels - 0001. #2 Fuel Oil
Emergency Generator Fuels - 2730. Biodiesel (E-Gen)
Emergency Generator Fuels - 2731. Diesel (E-Gen)
7a. If Waste/Used/Other Oils 9999. Other-Please list
8. Tank Type
Select Option
01. Steel/Carbon Steel/Iron
02. Galvanized Steel Alloy
03. Stainless Steel Alloy
04. Fiberglass Coated Steel
05. Steel Tank in Concrete
06. Fiberglass Reinforced Plastic (FRP)
07. Plastic
08. Equivalent Technology
09. Concrete
10. Urethane Clad Steel
99. Other
8a. If Other- Please list
9. Internal Protection
Select Option
00. None
01 Epoxy Liner
02. Rubber Liner
03. Fiberglass Liner (FRP)
04. Glass Liner
99. Other-Please list
9a. If 99. Other-Please list
10. External Protection
Select Option
00. None
01. Painted/Asphalt Coating
02. Original Sacrificial Anode
03. Original Impressed Current
04. Fiberglass
05. Jacketed
06. Wrapped (Piping)
07 Retrofitted Sacrificial Anode
08. Retrofitted Impressed Current
09. Urethane
99. Other-Please list
10a. If 99. Other-Please list
11. Tank Secondary Containment
Select Option
00. None
01. Diking (AST Only)
02. Vault (with access)
03. Vault (without access)
04. Double-Walled (UST Only)
05. Synthetic Liner
06. Remote Impounding Area
07. Excavation Liner
09. Modified Double-Walled (AST Only)
10. Impervious Underlayment (AST Only)
11. Double Bottom (AST Only)
12. Double-Walled (AST Only)
99. Other - Please list
11a. If 99. Other-Please list
12. Tank Leak Detection
Select Option
00. None
01. Interstitial Electronic Monitoring
02. Interstitial Manual Monitoring
03. Vapor Well
04. Groundwater Well
05. In-Tank System (Auto Tank)
06. Impervious Barrier/Concrete Pad (AST Only)
07. Statistical Inventory Reconciliation (SIR)
08. Weep holes in vaults with no access for inspection
99. Other-Please list
12a. If 99. Other-Please list
13. Tank Overfill Prevention
Select Option
00. None
01. Float Vent Valve
02. High Level Alarm
03. Automatic Shut-Off
04. Product Level Gauge (AST Only)
05. Vent Whistle
99. Other-Please list
13a. If 99. Other-Please list
14. Tank Spill Prevention
Select Option
00. None
01. Catch Basin
99. Other-Please list
14a. If 99. Other-Please list
15. Dispensing Method
Select Option
00. None
01. Pressurized Dispenser
02. Suction Dispenser
03. Gravity
04. On-Site Heating System (Suction)
05. On-Site Heating System (Supply/Return)
06. Tank-Mounted Dispenser
07. Loading Rack/Transfer Pump
16. Piping Location
Select Option
00. No Piping
01. Aboveground
02. Underground/On-ground
03. Aboveground/Underground Combination
17. Piping Type
Select Option
00. None
01. Steel/Carbon Steel/Iron
02. Galvanized Steel
03. Stainless Steel Alloy
04. Fiberglass Coated Steel
05. Steel Encased in Concrete
06. Fiberglass Reinforced Plastic (FRP)
07. Plastic
08. Equivalent Technology
09. Concrete
10. Copper
11. Flexible Piping
99. Other-Please list
17a. If 99. Other-Please list
18. Piping External Protection
Select Option
00. None
01. Painted/Asphalt Coating
02. Original Sacrificial Anode
03. Original Impressed Current
04. Fiberglass
05. Jacketed
06. Wrapped (Piping)
07 Retrofitted Sacrificial Anode
08. Retrofitted Impressed Current
09. Urethane
99. Other-Please list
18a. If 99. Other-Please list
19. Piping Secondary Containment
Select Option
00. None
01. Diking (Aboveground Only)
02. Vault (w/access)
04. Double-Walled (Underground Only )
06. Remote Impounding Area
07. Trench Liner
12. Double-Walled (Aboveground Only)
99. Other-Please list
19a. If 99. Other-Please list
20. Pipe Leak Detection
Select Option
00. None
01. Interstitial Electronic Monitoring
02. Insterstitial Manual Monitoring
03. Vapor Well
04. Groundwater Well
07. Pressurized Piping Leak Detector
09. Exempt Suction Piping
10. Statistical Inventory Reconciliation (SIR)
99. Other-Please list
20a. If 99. Other-Please list
21. Under Dispenser Containment (UDC) present?
Select Option
Y
N
Tank Information
A. System Operation
Is 'Permit to Operate' current, accurate and posted in a conspicuous place?
Select Option
Y
N
N/A
Is system operating properly?
Select Option
Y
N
N/A
Are monitoring/observation wells marked and secured?
Select Option
Y
N
X (no wells)
Have dispenser sumps been properly maintained?
Select Option
Y
N (accumulation of product)
X (no sump; not required)
1 (accumulation of water/debris)
2 (no access)
3 (sump required but not present)
For motor fuel tank systems with pressurized piping, are shear valves properly installed and operable?
Select Option
Y
N (no shear valve)
X (not pressurized piping)
1 (inoperative valve)
2 (improperly installed)
3 (no access)
Was the tank properly permanently closed or did it undergo a change-in-service?
Select Option
Y
N
X (active or out-of-service tank)
1 (tank closed w/o notification)
If the tank system is out-of-service, has it been out-of-service for more than 12 months?
Select Option
Y
N
X (active tank)
1 (permanently closed tank system)
Were any spills observed? (Include suspected releases from leak detection equipment and uninvestigated inventory discrepancies.)
Select Option
Y
N
Have tank top sumps been properly maintained?
Select Option
Y
N (accumulation of product)
X (no sump)
1 (accumulation of water/debris)
2 (no access)
Is there a 5 gallon spill bucket (catch basin) installed?
Select Option
Y
N
N/A
Have spill buckets been properly maintained?
Select Option
Y
N (accumulation of product)
X (no spill bucket)
1 (accumulation of water/debris)
2 (no access)
Is the fill port/tank color coded/marked to identify the product in the tank system?
Select Option
Y
N
X (day tank)
1 (incorrectly color coded/marked)
Does labeling meet Nassau County Dept. of Health standards?
Select Option
Y
N
N/A
Tank is labeled with tank working capacity, tank number, Facility I.D. #, contents and hazard signs?
Select Option
Y
N
N/A
High-level alarm can be easily seen and heard?
Select Option
Y
N
N/A
Tank has secondary containment
Select Option
Y
N
N/A
Daily inventory records are complete and have been kept for five years?
Select Option
Y
N
N/A
30-day release detection monitoring record is complete?
Select Option
Y
N
N/A
B. Pump Transfer Station
Is there a pump transfer station?
Select Option
Y
N
Is pipe bowing between supports?
Select Option
Y
N
N/A
Do all supports appear to be secure?
Select Option
Y
N
N/A
Are there any visible leaks?
Select Option
Y
N
N/A
Is there any visible corrosion?
Select Option
Y
N
N/A
Does anything (piping, valves, etc.) look unordinary or of concern, such as loose fittings, swelling gasket, exposed wire, etc.?
Select Option
Y
N
N/A
Aboveground Storage Tank System (AST)
A. Tank Condition
Are there any leaks or spills?
Select Option
Y
N
N/A
Are there any cracks/bulges/corrosion?
Select Option
Y
N
N/A
Are exterior tank surfaces painted?
Select Option
Y
N
N/A
Are gauge or high level alarm working?
Select Option
Y
N
N/A
Is leak detection equipment being monitored and inspected?
Select Option
Y
N
N/A
Is interstitial port labeled and locked?
Select Option
Y
N
N/A
Is cathodic protection monitored and inspected?
Select Option
Y
N
N/A
Is tank elevated on saddles?
Select Option
Y
N
N/A
Is tank in contact with ground?
Select Option
Y
N
N/A
Is tank partially buried?
Select Option
Y
N
N/A
Does anything (piping, valves, etc.) look unordinary or of concern, such as loose fittings, swelling gasket, exposed wire, etc.?
Select Option
Y
N
N/A
For Cat. 2 and 3 ASTs, does the AST meet standards?
Select Option
Y
N
X (Cat. 1 AST)
If not, how is the tank deficient?
Select Option
1 (tank not welded steel)
2 (no surface coating)
3 (tank resting on soil w/o cathodic protection)
4 (tank on grade w/o impermeable barrier)
5 (no leak monitoring between tank and barrier)
Is the cathodic protection system being evaluated regularly?
Select Option
Y
X (no CP system required)
1 (no annual survey)
2 (no 60-day inspection for impressed current systems)
3 (records not maintained)
4 (minimum protection not provided/failed annual survey)
5 (operator has not completed appropriate repair in response to test results)
For ASTs greater than 10,000 gallons (or ASTs less than 10,000 gallons within 500 feet of a sensitive receptor), is the secondary containment adequately designed and in good condition?
Select Option
Y
N (no secondary containment)
X (secondary containment not required)
1 (secondary containment not maintained)
2 (inadequate design)
For ASTs less than 10,000 gallons that are using alternatives to secondary containment, are DER-25 issues addressed?
Select Option
Y
N
X (not required/applicable)
1 (equipment not maintained)
Does the AST have a gauge, high-level alarm, high-level liquid pump cut-off controller, or an equivalent device?
Select Option
Y
N
1 (inoperative)
Is the tank marked with design and working capacities and tank ID number?
Select Option
Y
N
1 (incomplete label)
Does the facility conduct monthly inspections for all AST systems?
Select Option
Y
N
1 (records not maintained)
Does the facility conduct ten-year inspections for Cat. 1 AST systems?
Select Option
Y
N
X (not required per Part 613-4.3(a)(1)(iii) OR Cat. 2/3 AST system)
1 (records not maintained)
Does the facility conduct tightness testing at ten-year intervals for underground Cat. 1 piping?
Select Option
Y
N
X (Cat. 2/3 piping)
1 (test report not submitted)
B. Foundation/Structural
Is there any settlement/cracks/corrosion?
Select Option
Y
N
N/A
Are anchor bolts tight?
Select Option
Y
N
N/A
C. Secondary Containment
Are there any cracks/gaps/punctures/corrosion or areas of potential containment breech?
Select Option
Y
N
N/A
Is paint/sealant in good condition?
Select Option
Y
N
N/A
Is there stormwater build-up?
Select Option
Y
N
N/A
Stormwater discharge date
Is drainage valve locked closed?
Select Option
Y
N
N/A
Are dike drain valves locked in a closed position?
Select Option
Y
N (unlocked)
X (no dike/discharge pipe)
1 (no valve on discharge pipe)
D. Pipes/Valves/Pumps/Sumps
Are there leaks or spills?
Select Option
Y
N
N/A
Is there any corrosion/discoloration?
Select Option
Y
N
N/A
Are supports in good condition?
Select Option
Y
N
N/A
Are valves operational?
Select Option
Y
N
N/A
Are vents visually free from blockage or obstruction?
Select Option
Y
N
N/A
Is a solenoid or equivalent valve in place for gravity-fed motor fuel dispensers?
Select Option
Y
N
X (AST system not storing motor fuel OR dispensers not gravity-fed)
1 (inoperative)
2 (valve not adjacent to and downstream from the operating valve)
Is a check valve in place for pump-filled ASTs with remote fills?
Select Option
Y
N
X (no remote fill)
1 (inoperative)
Is an operating valve in place on every line with gravity head?
Select Option
Y
N
X (no gravity head on line)
1 (inoperative)
E. Sumps
Are manhole covers secured properly?
Select Option
Y
N
N/A
Are manhole covers gaskets in good condition?
Select Option
Y
N
N/A
Are the sumps free of product, debris, rainwater, dirt, etc.?
Select Option
Y
N
N/A
Are there any visible leaks?
Select Option
Y
N
N/A
Is there any visible corrosion?
Select Option
Y
N
N/A
Does anything (piping, valves, etc.) look unordinary or of concern, such as loose fittings, swelling gasket, exposed wire, etc.?
Select Option
Y
N
N/A
Are there sumps?
Select Option
Y
N
If more than one sump, list on diagram and identify AOC and sump #
Select Option
Completed
Not Completed
F. Tank Monitoring System
Is there a tank monitoring system?
Select Option
Y
N
Are sensors hard mounted?
Select Option
Y
N
N/A
Is system operating properly?
Select Option
Y
N
N/A
Does system pass routine test when depressing test button?
Select Option
Y
N
N/A
Are there any alarm conditions or concerns?
Select Option
Y
N
N/A
Does printer have paper?
Select Option
Y
N
N/A
Is printer working properly?
Select Option
Y
N
N/A
Print and attach test
Select Option
Completed
Not Completed
N/A
Are all visual and audible alarms working?
Select Option
Y
N
N/A
Remote Annuciator - Light and sound works
Select Option
Y
N
N/A
Is the main alarm panel properly labeled?
Select Option
Y
N
N/A
Does remote annunciator test sound/light when button is pressed?
Select Option
Y
N
N/A
Does sump test sound/light when button is depressed?
Select Option
Y
N
N/A
Does double wall test sound/light when button is depressed?
Select Option
Y
N
N/A
Does overfill alarm test sound/light when button is depressed?
Select Option
Y
N
N/A
G. Fill or Remote Fill Location
Is there a catch basin?
Select Option
Y
N
N/A
Is the catch basin aboveground?
Select Option
Y
N
N/A
Is the catch basin belowground?
Select Option
Y
N
N/A
Is there a remote fill?
Select Option
Y
N
N/A
If there is a remote fill, is the piping below ground?
Select Option
Y
N
N/A
Are remote fills locked?
Select Option
Y
N
N/A
Do all fill pipes have caps?
Select Option
Y
N
N/A
Are there any visible leaks?
Select Option
Y
N
N/A
Is fill port API color coded?
Select Option
Y
N
N/A
Is there a 5 gallon spill bucket (catch basin) installed?
Select Option
Y
N
N/A
Have spill buckets been properly maintained?
Select Option
Y
N (accumulation of product)
X (no spill bucket)
1 (accumulation of water/debris)
2 (no access)
Is the tank color coded/marked to identify the product in the tank system?
Select Option
Y
N
X (day tank)
1 (incorrectly color coded/marked)
Is there any visible corrosion?
Select Option
Y
N
N/A
Does anything (piping, valves, etc.) look unordinary or of concern, such as loose fittings, swelling gasket, exposed wire, etc.?
Select Option
Y
N
N/A
Underground Storage Tank System (UST)
A. Tank Condition
Are there any leaks or spills?
Select Option
Y
N
N/A
Are there any cracks/bulges/corrosion?
Select Option
Y
N
N/A
Are exterior tank surfaces painted?
Select Option
Y
N
N/A
Is tank labeled properly (design/working capacity/tank #)?
Select Option
Y
N
N/A
Is gauge or high level alarm working?
Select Option
Y
N
N/A
Is leak detection equipment monitored and inspected?
Select Option
Y
N
N/A
Is interstitial port labeled and locked?
Select Option
Y
N
N/A
Is cathodic protection monitored and inspected?
Select Option
Y
N
N/A
For Cat. 2 and 3 UST systems, does the UST system meet standards?
Select Option
Y
N
X (Cat. 1 UST system)
If not, how is the tank system deficient?
Select Option
1 (tank not corrosion-resistant)
2 (no tank secondary containment)
3 (no tank leak monitoring)
4 (no overfill prevention)
5 (piping not corrosion-resistant)
6 (no piping leak monitoring)
7 (no fill port label)
8 (as-built plans/drawings missing or incomplete)
9 (no secondary containment for Cat. 3 piping)
B. Leak Prevention
Is the spill prevention device (i.e., spill bucket) present and functional?
Select Option
Y
N (not present)
X (tank receives ≤25 gallons at one time)
1 (not functional - holes/cracks present)
2 (no access)
Is the overfill prevention device (i.e., automatic shut-off, high-level alarm, ball float valve) present?
Select Option
Y
N
X (tank receives ≤25 gallons at one time)
1 (unable to verify)
Is the overfill prevention device set to activate at an appropriate level?
Select Option
Y
N
X (tank receives ≤25 gallons at one time)
1 (unable to verify)
Is the overfill prevention device operational?
Select Option
Y
N
X (tank receives ≤25 gallons at one time)
If not
Select Option
1 (automatic shut-off not operational - device tampered with/inoperable; gauging stick in drop tube)
2 (high-level alarm not operational)
3 (alarm not audible/visible to driver)
Ball float is not operational because: 4 (Stage I vapor recovery is present)
Ball float is not operational because: 5 (piping system is suction)
Ball float is not operational because: 6 (drain valve on spill bucket is broken/impaired by debris, causing drain valve to act as an emergency vent)
Are metal tank system components in contact with soil (including fittings, connections, etc.) continuously protected from corrosion?
Select Option
Y
X (no metal tank system components)
If not
Select Option
1 (metal piping components - i.e., swing joints, flex-connectors, etc. - are not isolated from the ground/cathodically protected)
2 (Cat. 2/3 tanks or piping does not meet corrosion protection standards)
3 (Cat 1. steel tank is not internally lined/retrofitted with cathodic protection)
4 (Cat 1. metal piping is not retrofitted with cathodic protection)
Is the cathodic protection system (for steel tank and piping systems) tested within the required time frame and does it provide continuous protection?
Select Option
Y
X (CP not required)
If not
Select Option
1 (no CP test on either)
2 (no CP test on tank)
3 (no CP test on piping)
4 (records not maintained)
5 (minimum protection not provided/failed annual survey)
6 (inadequate monitoring - not enough readings)
7 (operator has not completed appropriate repair in response to test results)
If an impressed current system is in use, has the system been operated continuously?
Select Option
Y
X (no impressed current system)
If not
Select Option
1 (rectifier is not operational)
2 (rectifier does not have electrical power 24/7)
3 (clock shows that power has been turned off)
Is the impressed current system inspected every 60 days?
Select Option
Y
N
X (no impressed current system)
1 (at least 2 of last 3 readings not available)
For lined Cat. 1 USTs, is the internal lining being inspected periodically (i.e., within 10 years after installation and every 5 years thereafter)?
Select Option
Y
N (no report)
X (UST not lined OR Cat. 2/3 UST OR lining installed w/ CP)
1 (lining was inspected and failed)
2 (inspection procedure not acceptable)
If cathodically protected tank or piping was structurally repaired, were CP systems tested/inspected within 6 months after repair?
Select Option
Y
N
X (no CP system/structural repair)
Were structurally repaired tank and piping tested for tightness within 30 days after repair completion? (Tightness test not required when internal inspection is conducted after repair or if weekly leak detection method is in use.)
Select Option
Y
N
X (no structural repair)
C. TMS and Leak Detection
Is there a tank monitoring system?
Select Option
Y
N
Is system operating properly?
Select Option
Y
N
N/A
Does system pass routine test when depressing test button?
Select Option
Y
N
N/A
Are there any alarm conditions or concerns?
Select Option
Y
N
N/A
Does printer have paper?
Select Option
Y
N
N/A
Is printer working properly?
Select Option
Y
N
N/A
Print and attach test
Select Option
Completed
Not completed
N/A
Are all visual and audible alarms working?
Select Option
Y
N
N/A
Remote Annuciator - light and sound works
Select Option
Y
N
N/A
Is the main alarm panel properly labeled?
Select Option
Y
N
N/A
Does remote annunciator test sound/light when button is pressed?
Select Option
Y
N
N/A
Does sump test sound/light when button is depressed?
Select Option
Y
N
N/A
Does double wall test sound/light when button is depressed?
Select Option
Y
N
N/A
Does overfill alarm test sound/light when button is depressed?
Select Option
Y
N
N/A
Is sensor(s) hard mounted?
Select Option
Y
N
N/A
Is leak monitoring being performed?
Select Option
Y
N
X (single-walled, Cat. 1/2 piping is tested for tightness every 3 years/annually OR exempt suction piping)
1 (inoperative system)
2 (weekly leak detection records not maintained)
3 (monthly operability records not maintained)
4 (interstitial space on Cat. 2/3 tanks or Cat. 2/3 piping not monitored)
5 (leak monitoring method is inappropriate)
Specify method(s) of tank leak detection used
Select Option
A. Automatic Tank Gauging (ATG)
B. Manual Tank Gauging (MTG)
D. Inventory Monitoring (REQUIRED FOR UST SYSTEMS STORING MOTOR FUEL/KEROSENE FOR RESALE)
E. Groundwater or Vapor Monitoring
F. Interstitial Monitoring
H. Statistical Inventory Reconciliation (SIR)
Specify SECOND method of pressurized piping leak detection used aside from ALLD
Select Option
G. Automatic Line Leak Detector (ALLD) (REQUIRED)
C. Line Testing
E. Groundwater or Vapor Monitoring
F. Interstitial Monitoring
H. Statistical Inventory Reconciliation (SIR)
Specify method of suction piping leak detection used
Select Option
C. Line Testing
E. Groundwater or Vapor Monitoring
F. Interstitial Monitoring
H. Statistical Inventory Reconciliation (SIR)
X. Exempt Suction Piping (i.e., Safe/European Suction) / Siphon Bar (LD NOT REQUIRED)
Is the Automatic Tank Gauging (ATG) on the National Work Group on Leak Detection Evaluations list?
Select Option
Y
N
Is the ATG set up properly to conduct leak tests?
Select Option
Y
N
X (unable to confirm)
Did the ATG conduct leak tests while the tank contained the routinely highest level of product?
Select Option
Y
N
D. Manual Tank Gauging (MTG)
Is tank size appropriate for using MTG (under 1000 gal. only)?
Select Option
Y
N
N/A
Do records indicate that MTG is being conducted correctly?
Select Option
Y
N
N/A
Is MTG equipment capable of 1/8" measurement?
Select Option
Y
N
N/A
E. Pipes/Valves/Pumps/Sumps
Are there leaks or spills?
Select Option
Y
N
N/A
Is there any corrosion/discoloration?
Select Option
Y
N
N/A
Are supports in good condition?
Select Option
Y
N
N/A
Are valves operational?
Select Option
Y
N
N/A
Are vents visually free from blockage or obstruction?
Select Option
Y
N
N/A
F. Sumps
Are there sumps?
Select Option
Y
N
If more than one sump, list on diagram and identify AOC and sump #
Select Option
Completed
Not Completed
Are manhole covers secured properly?
Select Option
Y
N
N/A
Are manhole covers gaskets in good condition?
Select Option
Y
N
N/A
Are the sumps free of product, debris, rainwater, dirt, etc.?
Select Option
Y
N
N/A
Are there any visible leaks?
Select Option
Y
N
N/A
Is there any visible corrosion?
Select Option
Y
N
N/A
Does anything (piping, valves, etc.) look unordinary or of concern, such as loose fittings, swelling gasket, exposed wire, etc.?
Select Option
Y
N
N/A
G. Fill or Remote Fill Location
Is there a catch basin?
Select Option
Y
N
N/A
Is the catch basin aboveground?
Select Option
Y
N
N/A
Is the catch basin belowground?
Select Option
Y
N
N/A
Is there a remote fill?
Select Option
Y
N
N/A
If there is a remote fill, is the piping below ground?
Select Option
Y
N
N/A
Are remote fills locked?
Select Option
Y
N
N/A
Do all fill pipes have caps?
Select Option
Y
N
N/A
Are there any visible leaks?
Select Option
Y
N
N/A
Is Fill Port API Color Coded?
Select Option
Y
N
N/A
Is there a 5 gallon spill bucket (catch basin) installed?
Select Option
Y
N
N/A
Have spill buckets been properly maintained?
Select Option
Y
N (accumulation of product)
X (no spill bucket)
1 (accumulation of water/debris)
2 (no access)
Is the fill port/tank color coded/marked to identify the product in the tank system?
Select Option
Y
N
X (day tank)
1 (incorrectly color coded/marked)
Is there any visible corrosion?
Select Option
Y
N
N/A
Does anything (piping, valves, etc.) look unordinary or of concern, such as loose fittings, swelling gasket, exposed wire, etc.?
Select Option
Y
N
N/A
H. Line Testing
Does line testing apply?
Select Option
Y
N
Is line testing method on the National Work Group on Leak Detection Evaluations (NWGLDE) list?
Select Option
Y
N
Is line testing method being conducted according to the manufacturer's instructions? (Compare test report with NWGLDE specifications for the test method.)
Select Option
Y
N
Is line testing conducted within the appropriate time frame?
Select Option
Y
N
I. Inventory Monitoring
Is this a motor fuel or kerosene tank?
Select Option
Y
N
Does the facility have adequate inventory records for metered tanks storing motor fuel/kerosene that will be sold as part of a commercial transaction?
Select Option
Y
N
If not, which items are deficient?
Select Option
1 (no records)
2 (no tank bottom water measurements)
3 (equipment not capable of 1/8" measurement)
4 (meter not calibrated)
5 (no reconciliation of records)
6 (improper reconciliation)
7 (no investigation of discrepancy)
J. Groundwater/Vapor Monitoring
Does this site require groundwater/vapor monitoring?
Select Option
Y
N
Is there a site assessment report indicating location and number of groundwater/vapor monitoring wells?
Select Option
Y
N
Are wells properly designed and positioned?
Select Option
Y
N
1 (no report)
According to the site assessment report, is groundwater always detectable in the monitoring well (i.e., groundwater is never more than 20' from the ground surface)?
Select Option
Y
N
X (no groundwater monitoring wells)
1 (no report)
Is the vapor monitoring well not affected by high groundwater levels?
Select Option
Y
N
X (no vapor monitoring wells)
1 (no report)
K. Interstitial Monitoring
Does the tank have interstitial monitoring?
Select Option
Y
N
Does secondary containment appear to have integrity?
Select Option
Y
N
Is the sensor properly positioned in the sump?
Select Option
Y
N
X (manual monitoring)
L. Automatic Line Leak Detector (ALLD)
Is an ALLD in use?
Select Option
Y
N
Is the ALLD present and does it appear to be operational?
Select Option
Y
N (not present)
1 (not operational)
2 (no access)
Has the annual functionality test of the ALLD been conducted, and are records available?
Select Option
Y
N (no test conducted)
1 (no records)
M. Statistical Inventory Reconciliation (SIR)
Is the SIR method on the National Work Group on Leak Detection Evaluations (NWGLDE) list of leak detection methods?
Select Option
Y
N
Is SIR required for this site?
Select Option
Y
N
N. UST Operator Training
Is there a designated Class A Operator and is that person properly authorized?
Select Option
Y
N
1 (authorized Class A Operator is not designated)
2 (designated Class A Operator is not authorized)
3 (records are missing/inadequate)
Is there a designated Class B Operator and is that person properly authorized?
Select Option
Y
N
1 (authorized Class B Operator is not designated)
2 (designated Class B Operator is not authorized)
3 (records are missing/inadequate)
Is there a designated Class C Operator and is that person properly trained?
Select Option
Y
N
1 (authorized Class C Operator is not designated)
2 (designated Class C Operator is not authorized)
3 (records are missing/inadequate)
O. UST Closure
If the tank is permanently closed or underwent a change-in-service within the last 3 years, was a site assessment performed?
Select Option
Y
N
X (not applicable)
1 (site assessment is inadequate)
For Cat. 2 and 3 UST systems, does the UST system meet standards?
Select Option
Y
X (Cat. 1 UST system)
If not, how is the tank system deficient?
Select Option
1 (tank not corrosion-resistant)
2 (no tank secondary containment)
3 (no tank leak monitoring)
4 (no overfill prevention)
5 (piping not corrosion-resistant)
6 (no piping leak monitoring)
7 (no fill port label)
8 (as-built plans/drawings missing or incomplete)
Is cathodic protection for steel tank and piping systems monitored annually?
Select Option
Y
N (no CP test on either)
X (CP not required)
1 (no CP test on tank)
2 (no CP test on piping)
3 (records not maintained)
4 (minimum protection not provided/failed annual survey)
5 (inadequate monitoring - not enough readings)
6 (operator has not completed appropriate repair in response to test results)
Is leak monitoring being performed?
Select Option
Y
N
X (Cat 1 tank or Cat 1 piping is tested for tightness annually OR Cat 1 tank stores No. 5/6 fuel oil)
1 (inoperative system)
2 (weekly leak detection records not maintained)
3 (monthly operability records not maintained)
4 (interstitial space on Cat. 2/3 tanks not monitored)
5 (leak monitoring method is inappropriate)
For Cat. 1 UST systems, has tightness testing been conducted within the last year?
Select Option
Y
N (no test on either tank or line)
X (exempt from tightness testing)
1 (no tank test)
2 (no line test)
3 (test report not submitted)